- Air-Compressor Parts[10]
- Other Air Cleaning Equipment[10]
- Other Refrigeration & Heat Exchange Equipment[3]
- Other Machinery[1]
- Air-Compressors[10]
- Gas Generation Equipment[1]
- Refrigeration & Heat Exchange Parts[1]
- Drying Equipment[4]
- Other Industrial Filtration Equipment[1]
- Air Filter[5]
- Industrial Chiller[10]
- Moulds[1]
- Industrial Air Conditioners[1]
- Contact Person : Mr. cai zong
- Company Name : Hangzhou Kelin Aier Qiyuan Equipment Co., Ltd.
- Tel : 86-571-88790991
- Fax : 86-571-88792222
- Address : Zhejiang,Hangzhou,industry garden,anxi area yuhang,Hangzhou city,China
- Country/Region : China
- Zip : 311113
reciprocating compressor type chiller
Features
Mature technology and reliable operation
Advanced compressors
Dual Refrigerant circuits and multicompressors arrangement ensures reliable system operation and flexible control.
Compressor running time balancing.
Efficient heat exchangers with enhanced heat transfer tubes.
Multi safety protection functions.
Convenient installtion and ease of use
Item | Water cooled Reciprocating Chiller | |||||
Model | LSB200 | LSB240 | LSB280 | LSB360 | LSB420 | LSB560 |
Cooling Capacity | 181.2 KW | 230.8kw | 271.8kw | 346.2kw | 407.7kw | 543.6kw |
Compressor Power | 35HP×2 | 40HP×2 | 50HP×2 | 40HP×3 | 50HP×3 | 50HP×4 |
Compressor Quantity | 2 sets | 2 sets | 2 sets | 3 sets | 3 sets | 4sets |
Flow of Chilled water | 31.3m3/h | 39.7m3/h | 46.7m3/h | 59.5 m3/h | 70.1 m3/h | 93.5m3/h |
Inlet/outlet connection of chilled water | 2.5" | 3" | 3" | 4" | 4" | 4" |
Flow of cooling water | 49.9 m3/h | 63.7m3/h | 74.9m3/h | 95.6 m3/h | 112.4 m3/h | 149.8m3/h |
Inlet/outlet connection of cooling water | 3" | 4" | 4" | 5" | 5" | 5" |
Dimensions L×W×H(mm) | 3400×830×1550 | 3800×830×1550 | 3800×830×1550 | 4300×1050×1550 | 4800×1050×1550 | 4500×1250×1600 |
Weight | 1800kg | 1950kg | 2020kg | 2800kg | 3100kg | 3800kg |
Refrigerant | R22 | |||||
Voltages | 380V/3PH/50HZ | |||||
Startup method | Direct startup, automatic control | |||||
Safety protections | High voltage, low voltage, oil pressure, water shortage, overloading, lack of phase, low water temp. etc. |
Cooling condition:
Temp. of inlet chilled water . 12 deg c; Temp. of outlet chilled water 7deg c
Temp. of inlet cooling water . 30deg c ; Temp. of outlet cooling water 35deg c
reciprocating compressor type chiller