Cascade liquid Chiller
Introudction
LSDD-F Series Air-cooled ultra low temperature chiller is mainly composed of cooling circulation system, freezing circulation system,high temperature refrigerating system,
low temperature refrigerating system, intelligent control system.
Cooling circulation system:Adopts high-efficient copper tube + fin condenser and outer rotor fan.
Freezing circulation system: chilled pump,chilled tank,shell tube or stainless steel plate heat exchanger, pipe and heat insulator.
Refrigerating circulation system(high and low temperature grades):hermetic or semi-hermetic reciprocating compressor,heat exchanger, solenoid valve,expansion valve etc.
Intelligent control system: PLC+touch screen/ text panel+ actuator+ control caninet
Features
Multiple protections:compressor reverse-phase,phase loss,over current,over temperature,oil pressure protections; refrigerating fulid protection and system voltage protection etc.
Control performance: reliable PLC controller,interlligent ,easy operation
Temperature range: 0 deg c to -75 deg c
Temperature precision :±1 deg c
Working conditions:
Ambient temperature: -5 deg c ~ 40deg c
Voltage: AC: (380 ± 10%) V, 50/60Hz, three-phase five-wire system
Application fields
Widely used in plastics, electroplating, ultrasonic, printing, machinery manufacturing, electronics, chemical, pharmaceutical,
military industry, scientific research, etc.
Model (LSDD) | -2.0F | -2.4F | -3.3F | -4.5F | -6.5F | -8.0F | -10F | -12F |
Rated cooling capacity (KW) | 2.0 | 2.4 | 3.3 | 4.5 | 6.5 | 8.0 | 10 | 12 |
Input power(KW) | 3.7 | 4.8 | 5.9 | 7.4 | 10 | 16.6 | 25.7 | 33.1 |
Current(A) | 7.0 | 9.1 | 11.2 | 14.1 | 19.2 | 31.6 | 48.8 | 62.9 |
Flow of liquid(m3/h) | 1 | 1 | 1 | 2 | 2 | 3 | 3 | 4 |
Connection(mm) | 25 | 25 | 25 | 25 | 25 | 40 | 40 | 40 |
Cooling conditions: condensing temperature: 45°C;evaporating temperature: -75°C; liquid outlet temperature: -70°C Refrigerating fluid: alcoholic solution |
Cascade liquid Chiller